35KV Power Transformer Types, Specifications, and Selection Guide

Author: Jeremiah

Aug. 11, 2026

92 0

Tags: Electrical Equipment & Supplies

35kV Power Transformer Types, Specifications, and Selection Guide

A 35kV power transformer is a medium-voltage transformer designed to transfer electrical energy between voltage levels while providing the voltage ratio, insulation system, thermal capacity, and installation configuration required by a power network. In practice, buyers commonly compare oil-immersed and dry-type designs, on-load or off-circuit tap arrangements, three-phase ratings, cooling methods, and application-specific protection requirements. I use this guide to help engineering teams, EPC contractors, utilities, and industrial buyers evaluate a 35kV transformer before requesting a quotation from Liye or another qualified supplier.

You can find more information on our web, so please take a look.

The correct selection depends on more than the nominal voltage. I recommend confirming the system’s highest operating voltage, rated power in kVA or MVA, frequency, insulation level, short-circuit duty, cooling conditions, tap range, installation environment, and applicable standards. The final specification should be reviewed by a qualified electrical engineer and coordinated with the local grid operator or project authority.

Who This 35kV Transformer Guide Is For

This guide is intended for procurement managers, electrical engineers, project developers, distributors, utility contractors, and industrial users sourcing transformers for medium-voltage distribution or substation projects. It is also useful for buyers who need to convert a basic request, such as “35kV transformer,” into a complete technical inquiry. I focus on the specifications that materially affect safety, compatibility, delivery, and lifecycle cost.

A 35kV transformer may be used in a utility substation, renewable-energy collection network, mining site, manufacturing plant, commercial facility, or infrastructure project. The required design can change significantly between an indoor plant room, an outdoor substation, a coastal location, and a high-altitude installation. For this reason, I do not recommend selecting a transformer from voltage alone.

35kV Transformer Basics and Voltage Classification

The term “35kV” generally describes the nominal voltage class of the connected medium-voltage system. It does not mean that every winding, bushing, accessory, or test value should be rated at exactly 35kV. A complete design must also identify the highest voltage for equipment, power-frequency withstand voltage, lightning impulse withstand level, neutral arrangement, and system earthing method.

IEC 60038 provides standard voltage information, while IEC 60076 covers power transformers and related technical requirements. In North American projects, IEEE C57 standards may also be relevant. Because national adoption and project specifications can differ, I recommend listing the governing standard edition and testing requirements in the purchase specification rather than relying on the phrase “35kV transformer” alone.

How a 35kV Transformer Works

A transformer transfers alternating-current energy between windings through electromagnetic induction. The turns ratio determines the approximate voltage relationship, while the transformer rating determines the apparent power that can be delivered under specified thermal and operating conditions. A step-down unit may reduce a 35kV distribution voltage to a lower utilization voltage, while a step-up unit may raise generator voltage for collection or transmission.

Transformers do not normally change frequency, and they cannot compensate for an incorrectly designed protection system. Voltage regulation, impedance, losses, inrush current, harmonics, and fault withstand must therefore be considered together. IEC 60076-1 identifies general requirements for power transformers, but the project engineer must still define the application-specific duty.

Main 35kV Power Transformer Types

Oil-Immersed 35kV Transformers

Oil-immersed transformers use insulating liquid for electrical insulation and heat transfer. They are widely considered for outdoor substations, utility distribution, renewable-energy projects, and industrial facilities where higher ratings or outdoor installation are required. Common configurations include sealed-tank designs and conservator-type designs, depending on the project’s maintenance philosophy and technical specification.

Important oil-immersed options include mineral-oil and alternative insulating-liquid designs. The choice affects fire planning, environmental controls, maintenance procedures, and total cost. I recommend asking the supplier to identify the liquid type, dielectric requirements, environmental declarations, containment expectations, and disposal or replacement procedures.

Dry-Type 35kV Transformers

Dry-type transformers use solid insulation and air or another non-liquid cooling medium instead of an insulating oil tank. They may be suitable for indoor substations, commercial buildings, tunnels, hospitals, and industrial areas where liquid containment or fire-risk constraints influence the design. However, the suitability of a dry-type transformer depends on the required rating, enclosure, ventilation, altitude, ambient temperature, and system insulation requirements.

Cast-resin and other dry-type constructions should not be selected solely because they are described as “maintenance-free.” They still require inspection, cleaning, temperature control, connection checks, and protection coordination. For indoor use, I recommend confirming the enclosure degree of protection, room ventilation, noise expectations, fire design requirements, and access for installation.

Two-Winding and Three-Winding Designs

A two-winding transformer has one high-voltage winding and one low-voltage winding. It is a common arrangement for substation step-down service. A three-winding transformer can connect three voltage levels or provide a dedicated tertiary winding for auxiliary loads, reactive equipment, or system-specific functions.

Three-winding designs can reduce the need for multiple separate transformers, but they normally require more detailed impedance, loading, fault-level, and protection studies. I recommend supplying the expected loading of each winding in MVA, the simultaneous-load condition, and the required vector group before requesting a firm quotation.

Key 35kV Transformer Specifications

Specification What It Defines Buyer Action
Nominal voltage Normal system voltage, such as 35kV State high-voltage and low-voltage winding values
Rated power Continuous apparent-power capacity in kVA or MVA Provide present load, future growth, and duty cycle
Frequency System operating frequency, commonly 50Hz or 60Hz Confirm the project frequency before design approval
Tap range Permitted voltage adjustment around the nominal ratio Define tap position, range, and operating method
Impedance Voltage-drop and fault-current-related transformer characteristic Coordinate with short-circuit and parallel-operation studies
Cooling method Heat dissipation arrangement, such as ONAN or ONAF Check ambient temperature and overload expectations

Rated Voltage and Insulation Level

For a 35kV system, I normally ask the buyer to specify nominal voltage, highest voltage for equipment, insulation withstand levels, and the required external insulation coordination. The bushing rating, cable termination, surge arrester, switchgear, and transformer insulation must be compatible. A mismatch can create avoidable commissioning and protection problems even when the nameplate includes “35kV.”

Rated Power and Thermal Performance

Transformer capacity is usually expressed in kVA or MVA rather than kW because transformer loading includes reactive power. For example, a project may require a 5MVA, 10MVA, or 20MVA unit, but the appropriate size depends on measured demand, motor starting, renewable intermittency, ambient conditions, and future expansion. I recommend documenting the normal load, emergency load, daily profile, expected power factor, and permissible overload duration.

Cooling design also matters. ONAN means oil natural circulation and air natural circulation, while ONAF adds forced-air cooling. A transformer with a 10MVA natural-cooling rating and a higher forced-air rating must be evaluated with its fan controls, redundancy, noise, auxiliary power, and maintenance requirements clearly stated.

Frequency, Vector Group, and Phase Arrangement

Common project frequencies include 50Hz and 60Hz, and a transformer designed for one frequency should not be assumed suitable for the other without confirmation. The vector group defines phase displacement and winding connection, such as delta or star, and it affects parallel operation, grounding, harmonics, and protection. The buyer should also specify three-phase operation, neutral access, neutral grounding equipment, and any requirement for a tertiary winding.

Liye supply professional and honest service.

Tap Changer and Voltage Regulation

An off-circuit tap changer requires the transformer to be de-energized before the tap position is changed. An on-load tap changer can adjust the ratio while energized, but it adds control, switching, maintenance, and cost considerations. Typical tap ranges must be stated by the project engineer; a range such as plus or minus 2 times 2.5% should never be assumed without confirming the grid-voltage study and supplier design.

Losses, Impedance, Noise, and Accessories

No-load loss, load loss, impedance, temperature rise, sound level, and partial-discharge requirements can materially affect lifecycle performance. I recommend requesting guaranteed values in the technical schedule and identifying the measurement method and tolerance. Accessories may include a pressure relief device, oil level indicator, winding-temperature indicator, oil-temperature indicator, Buchholz relay, marshalling box, surge protection interfaces, fans, and control panels, depending on the transformer construction.

IEC 60076-2 addresses temperature-rise requirements, while IEC 60076-5 addresses the ability of transformers to withstand short circuit. These references are useful when reviewing a supplier’s technical offer, but the applicable contract specification and local regulations remain controlling. I recommend treating accessory lists and testing requirements as part of the transformer scope, not as informal afterthoughts.

Matching Transformer Type to the Application

Application Design Questions Potentially Suitable Direction
Outdoor utility substation Weather exposure, fault level, cooling, maintenance access Often oil-immersed, subject to rating and local requirements
Indoor industrial plant Fire strategy, ventilation, noise, room dimensions Dry-type or oil-immersed with approved containment
Solar or wind collection system Variable loading, harmonics, step-up ratio, outdoor conditions Project-specific oil-immersed or dry-type design
Mining or remote site Dust, altitude, transport, spare parts, service access Ruggedized design with defined environmental limits

For renewable-energy projects, I recommend examining voltage variation, converter harmonics, frequent load changes, collector-circuit arrangement, and transformer energization behavior. For motor-heavy industrial sites, starting current and voltage dip may be more important than average demand. For remote projects, transport dimensions, lifting points, spare accessories, local service capability, and commissioning support can be as important as the transformer’s electrical rating.

A Practical 35kV Transformer Selection Framework

Step 1: Define the Electrical System

Start with the nominal voltage, highest system voltage, frequency, phase arrangement, grounding method, short-circuit level, and required insulation coordination. Include the upstream and downstream switchgear ratings so that the transformer is not evaluated as an isolated item. A single-line diagram and load schedule usually provide the supplier with a much stronger design basis than a short product description.

Step 2: Calculate Capacity and Future Demand

List the connected load, maximum demand, power factor, diversity, motor-starting requirements, renewable output profile, and planned expansion. Avoid selecting capacity only from today’s average load, but also avoid excessive oversizing that increases purchase cost and no-load losses. I recommend comparing at least two capacity scenarios and documenting the assumptions behind each one.

Step 3: Select Construction and Cooling

Compare oil-immersed and dry-type designs using the full installation context. Consider fire separation, environmental containment, ventilation, ambient temperature, altitude, maintenance resources, noise, footprint, and transport route. The lowest initial quotation may not be the lowest total-cost choice if installation modifications or specialized maintenance are later required.

Step 4: Confirm Taps, Vector Group, and Impedance

Use the voltage study to define the tap range and tap-changer type. Use the short-circuit and protection studies to define impedance, fault withstand, and coordination requirements. If parallel operation is planned, confirm matching ratios, vector groups, phase displacement, impedance tolerances, and tap positions before ordering.

Step 5: Establish Testing and Documentation

A purchase specification should identify routine tests, type or special tests where required, inspection points, drawings, nameplate information, manuals, test reports, packing requirements, and commissioning documents. Possible tests may include winding-resistance measurement, ratio verification, polarity or phase-relation checks, impedance measurement, dielectric tests, and no-load or load-loss measurements, subject to the governing standard and contract scope.

IEC 60076-3 covers insulation levels, dielectric tests, and external clearances for power transformers. I recommend asking the supplier to map each requested test to the applicable standard clause or project requirement. This makes technical-bid comparison more transparent and reduces disagreement during factory acceptance.

Common Buyer Mistakes

  • Specifying only “35kV transformer”: This omits rated power, frequency, insulation level, vector group, cooling, tap arrangement, and environmental conditions.
  • Ignoring the highest voltage for equipment: Nominal system voltage alone does not define the complete insulation design.
  • Choosing capacity from average load: Starting current, peak demand, power factor, and future expansion can change the required rating.
  • Leaving impedance undefined: An unsuitable impedance can affect fault current, voltage regulation, and parallel operation.
  • Assuming dry-type means zero maintenance: Ventilation, cleanliness, connections, temperature, and protection still require attention.
  • Comparing quotations without equal scope: Accessories, tests, packing, delivery, commissioning, and spare parts may differ between offers.

Pricing, MOQ, and Lead-Time Considerations

The price of a 35kV power transformer depends on rated power, winding material, insulation system, core design, tap changer, cooling arrangement, accessories, testing, enclosure, and delivery requirements. Copper or aluminum windings, for example, can lead to different weight, loss, cost, and design outcomes, but the decision should be based on the complete guaranteed performance rather than conductor material alone.

There is no universal lead time or minimum order quantity for every 35kV transformer. A standard configuration may be easier to schedule than a unit requiring special dimensions, unusual vector groups, high-altitude design, nonstandard tap ranges, or additional tests. I recommend requesting a quotation that separates engineering approval, material procurement, manufacturing, testing, packing, shipment, and site commissioning milestones.

How to Evaluate a 35kV Transformer Supplier

When I evaluate a supplier, I check whether the company can translate the project’s single-line diagram and technical schedule into a traceable design proposal. I also compare the supplier’s manufacturing information, quality-control process, test documentation, drawing-review procedure, packaging method, and after-sales support. Buyers should request verifiable documents rather than relying on unsupported claims about quality or performance.

Supplier Evaluation Checklist

  • Can the supplier provide a complete datasheet and clearly identify deviations?
  • Are the proposed standards and test requirements stated in writing?
  • Does the quotation include all required accessories and control interfaces?
  • Can the supplier confirm winding connection, vector group, impedance, tap range, and cooling class?
  • Are routine-test reports and inspection records included in the agreed scope?
  • Can the supplier support drawings, installation guidance, commissioning, and spare-parts planning?
  • Are transport dimensions, total weight, lifting points, and site limitations documented?

How Liye Can Support a 35kV Transformer Inquiry

At Liye, I recommend beginning with the buyer’s technical requirements rather than proposing a generic 35kV model. Our quotation process can be structured around the required voltage ratio, MVA rating, frequency, vector group, tap arrangement, insulation level, cooling method, installation environment, accessories, testing, and delivery destination. Where the project specification is incomplete, we can identify the missing information that should be confirmed by the project engineer.

For a practical technical review, I suggest preparing the single-line diagram, load schedule, site altitude, ambient-temperature range, indoor or outdoor installation details, short-circuit level, preferred standard, and required delivery date. Liye can then organize the inquiry into a technical datasheet and commercial scope for easier comparison. Final design acceptance, protection coordination, and grid compliance should remain subject to the responsible engineering authority.

Key Takeaways

  • A 35kV transformer is selected by system requirements, not nominal voltage alone.
  • Oil-immersed and dry-type designs serve different installation, fire, maintenance, and rating needs.
  • Critical data includes MVA or kVA rating, frequency in Hz, insulation level, impedance percentage, vector group, cooling class, and tap range.
  • Short-circuit duty, transformer losses, temperature rise, accessories, testing, and transport requirements should be written into the purchase specification.
  • A comparable supplier quotation should include technical deviations, test scope, drawings, delivery milestones, and after-sales responsibilities.

Conclusion: Choosing the Right 35kV Power Transformer

The right 35kV power transformer is the design that matches the electrical network, installation environment, operating profile, safety strategy, and lifecycle requirements. I recommend completing the system data sheet first, comparing oil-immersed and dry-type options against the actual site conditions, and confirming capacity, insulation, impedance, taps, cooling, testing, and accessories before commercial evaluation. This approach gives the buyer a more reliable basis for technical approval and procurement.

To start a Liye inquiry, send the required voltage ratio, rated power, frequency, vector group, tap requirements, installation location, environmental conditions, applicable standard, testing expectations, and delivery destination. Our team can use this information to prepare a project-specific technical and commercial response for your 35kV power transformer requirement.

Reference framework: IEC 60038, IEC 60076-1, IEC 60076-2, IEC 60076-3, and IEC 60076-5; IEEE C57 standards may apply where specified by the project or regional authority.